How much is the optimum power supply needed for SYNC2000-S6R1?
Can I use all the six serial ports in both RS232 and RS485 mode?
NO, S1-S4 can use either as RS232 or RS485, but S5-S6 can be used only as RS232.
How to change the serial ports from RS232 to RS485 mode in SYNC 2000?
Change the internal DIP switches to ON position.
Which are the serial ports supporting full modem signals in SYNC 2000?
Only port S1 supports full modem signals.
I purchased SYNC2000-S4R1. But the sticker/label on the gateway refers SYNC2000-S6R1. Why?
The gateway you got is SYNC2000-S6R1, but among the 6 serial ports in gateway only 4 are licensed.
How can I use the console port available in SYNC?
You can use one serial DB9 to RJ45 cross cable to connect with the console port of the gateway.
Baud Rate – 115200
Data Bit – 8 Stop Bit – 1
Parity – None
Flow Control – None
What is the internal memory capacity of SYNC2000-S6R1?
The internal memory is 32MB RAM, 256MB Flash
Is it possible to increase the memory of SYNC2000-S6R1?
What is the internal memory capacity of SYNC2000-S6R1?
The internal memory is 32MB RAM, 256MB Flash
What is the purpose of green and orange LEDs in the serial ports?, and how they differ from that of Ethernet port?
Ethernet Port
Green LED : 100Mbps Ethernet connection
Green LED Off: Link is inactive.
Green LED On : Link is active.
Yellow LED : 10Mbps
Yellow LED Off: Link is inactive
Yellow LED On: Link is active.
Serial Port
Green LED : Serial port is transmitting data
Yellow LED: Serial port is receiving data
OFF : NO data transmitted/received through serial port
Will SYNC2000-S6R1 lose time synchronization after the recovery of Power Failure
The Gateway time is always changing after each gateway restart. Why?
The Gateway has an RTC Backup Battery. The Battery might be drained .Replace the (Lithium 3V) battery.
Is there any option in EC to check the port failure?
How much time it take to boot up after a power reset?
About 10-15 seconds for boot u, this can be checked using ping
In SYNC 2000, does the time taken by the gateway to start communication after a power reset depends on the protocols/COnfig used?
Yes, Initialization time will depend on the number of rows in the profile as well as the number of tags mapped.
What is the power supply input for SYNC3000-S4R2?
How can I use SD Card Slot and USB port on SYNC3000-S4R2?
The SD Card Slot and USB port are for future use
How can I use the console port of SYNC3000-S4R2?
Console port is a serial port used for debugging critical issues. The login and other information can be obtained from KALKITECH Support team: support@kalkitech.com.
A serial cross cable should be used. The RS232 settings are: Baud Rate – 115200, Data Bit – 8 Stop, Bit – 1, Parity – None, Flow Control – None
How can I use the DIs and DOs available on SYNC3000-S4R2?
The DIs and DOs available on SYNC3000-S4R2 are for future use.
In SYNC 3000, how can we use a serial port in RS485 mode?
The serial port settings for the corresponding channel in EasyConnect should be changed to RS485 mode
Should I press "Reset to default" button if my configuration/settings in gateway is not working?
No, do not press in any case "Reset to default" button, since it takes the gateway back to default state without any firmware.
Please contact KALKITECH Support team: support@kalkitech.com
I want to use one Ethernet port for DNP TCP and other for IEC61850. How can I do it?
There is no mapping/link between the Channels and the Ethernet ports (LAN1, LAN2).Each channel uses the interface (LAN1 or LAN2) with which it can reach the destination.
How many points can we configure in SYNC3000-S4R2? Can I get information about number of points configurable in other gateway models you provide?
Refer the table below for details:
Gateway Model No of points supported
IEC 61850/ICCP/SPA Other Protocols
SYNC2000-(S6R1/
S2R1,SYNC3000 (S4R2) 800 3000
SYNC 3000-
SYNC 3000 (S4R2) 1500 6000
SYNC 3000 S8R2 2000 8000
SYNC 3000 S16R2 2500 10000
SYNC3000S16R4 2500 10000
SYNC/S 500 1000
How to get the license for SCL Manager?
SCL Manager is a comprehensive engineering tool that allows user to manage the SCL engineering process with enhanced workspace, database with various IED's and its features, various SLD templates, and wizards for engineering purposes.
How to install the software, SCL Manager?
SCL Manager as well as ICD manager will install using the same installation file. User can download the latest database from the Kalkitech website.
How to get the key for SCL Manager?
You need to get the primary key of the machine by clicking on the obtain license button on the 'Application control panel' and fill the required information. On submitting you can save the primary key in your machine and send that file to support@kalkitech.com Kalkitech support team will send you the actual license for your machine which you can install using install license option in application control panel.
How can I describe a substation specification (create an SSD) file?
You can describe a substation specification description by adding the substation and its internal elements in the sld draw area/SCL tree or by importing the template from the SLD library. Then you can export the SSD file by selecting the export option of the substation
How can I describe an IED capability (create an ICD) file in SCL Manager?
Create an SCL project and add an IED using the IED wizard. For creating ICD file for a new IED, you can opt for 'Create new' option of the IED Wizard; select the functions supported by the IED. There you have your IED. You can Export the ICD/CID file by right clicking the IED in Project explorer or from SCL tree.
In SCL Manager, will the ICD files validate during loading?
SCL Manager will validate for all files while loading/importing in accordance with the SCL file schema version 1.4
What are SCL, SLD and IED folders in the SCL project workspace?
SCL, SLD and IED folders are the default folders which will come with a new SCL project. SCLfolder contains the SCL file of the project, SLD folder contains all the single line diagrams, IED folder contains all the IED and related files on default
Which are the editors that SCL Manager supports internally?
SCL Manager supports xml editor and rtf editor.
What is the optimum power supply input for SYNC-S1OEM?
RTS-CTS is not working in SYNC-S1OEM. Why?
Default firmware for SYNC-S1OEM does not support these signals. These should be separately enabled in software. Please contact support for more information
Can the OEM module control the transmission direction through hardware?
No. The transmission direction control should be done in the external circuitry
Do you have an orientative schematic for RS-485 coupling with the SYNC OEM module?
Is there an RTC available in SYNC-S1OEM?
What is the default IPs for the SYNC Gateways?
The Default IPs of SYNC interfaces are as given below:
Availability of the interfaces depends on the model of the gateway.
• eth0 - 192.168.0.121
• eth1 - 192.168.1.121
• eth2 - 192.168.2.121
• eth3 - 192.168.3.121
How can I change IP of the gateway?
The IP of the gateway can be changed by using "IP Configuration" option available in EasyConnect.
How can I get firmware and EasyConnect for the gateway purchased?
The gateway comes shipped with firmware. A CD will be shipped along with the gateway with EasyConnect Setup.
Can we redistribute the Kalki EasyConnect software configuration to our end users?
Yes, on agreement with the Software license terms.
I am not able to get the gateway in SCAN. What I should do?
The antivirus software or firewall may be blocking the multicast messages. Please disable these and try once again.
Which are the gateway models with serial port surge protection?
SYNC SxR1 gateway models have surge protection.
What is the console port? Is it Ethernet port or Serial port? How to use & What type of cable must I use?
Console port is a serial port used for debugging critical issues.
The login and other information can be obtained from KALKITECH Support.
A serial cross cable should be used, the RS232 settings in given below:
• Baud Rate – 115200
• Data Bit – 8
• Stop Bit – 1
• Parity – None
• Flow Control – None
What is the serial port pin configuration for the gateway?
Please refer SYNC user manual for details
I have a SYNC2000-S6R1 and SYNC3000-S4R2. Are the serial port pin outs the same?
No. The pin outs are different for the modules specified. Please refer SYNC User Manual for details.
I want to change the dip switch settings in the gateway for converting the serial port to RS485 mode. But there is a "Warranty Void if removed" seal. What should I do?
For setting the jumper, the gateway enclosure can be removed. To retain the warranty, send a mail to kalki support team: support@kalkitech.com with gateway serial no to get the confirmation.
How to set Timezone in the Gateway?
In Easyconnect, use the setting option 'Time Zone Info.
When I set the timezone through EasyConnect, the error "Cannot set timezone" is displayed?
It is dependent on geographical area, so please send a mail to support@kalkitech.com
What is the process for sending the converter back as RMA?
Send a mail to support team: support@kalkitech.com with details such as (S/N, Gateway Model, and PO etc). Kalkitech delivery team will provide the RMA form; fill in the relevant details along with the consignment.
Do KALKITECH have embedded OEM modules with 100BASE-FX Fiber Optic ethernet port?
Do KALKI gateways have EMI/EMC, 61850 certification?
SYNC SxR1 / SYNC2000 models are with EMI/EMC compliance and SYNC series of gateways are has IEC61850 level A certificate from CPRI. The IEC61850 certification from KEMA is in progress.
How can I add protocols to my existing Gateway?
Please contact KALKITECH Sales sales@kalkitech.in for purchasing new protocol licenses.
What is the limit for the number of Channels in SYNC?
What is the Limit for the number of nodes in SYNC?
The number of nodes in a channel is physical layer depended. In case of Serial RS485 multidropped energy meters, the maximum number of nodes can be only 31. For TCP channels it can have more no of nodes provided it should not cross the max point supported by a gateway.
What is the expected functionality of Diagnostic Point Event ?
The diagnostic point reports an event each time a node comes online or offline. This point can be mapped to the slave protocols for checking the communication status of the master protocol.
What is the expected functionality of the Status change Event?
The status change event is used to get a point reported as an event when its quality changes.
What are the general types of conversion - mapping supported in SYNC gateways?
The possible conversions can be mapped from Easyconnect. The details of a particular data type in a protocol can be checked in the protocol user manual.
How is quality of the point mapped from one protocol to another?
The Appendix K in SYNC user manual viz 'Flag conversion in SYNC' details the quality mapping.
What is the optimum power supply input for SYNC-S4R1OEM?
Can the module control the RS485 transmission direction through the S4R1 OEM hardware?
Yes. It uses the RTS signal for direction control.
If the power off period in S4R1 OEM is 1-2 sec will it affect the ping/ further communication of gateway
Do you have a version of the SYNC S4-OEM that has an edge finger connection instead of the J2 20 pin header?
No, we do not support the edge finger connection at present.
When I use the EasyConnect Scan function I receive information back from the Kalki SYNC S4-OEM that reports that the Model is a SYNC2000-S6R1?
SYNC S4 OEM is an OEM version of SYNC2000-S6R1. The firmware and configuration for both the models are the same, hence it reports as SYNC2000-S6R1
What is the maximum number of datasets that can be created in SYNC S4-OEM?
The maximum no of datasets that can be created in SYNC S4-OEM is 15 with maximum tags per dataset as 50; also the total no of tags which can be configured is 800 which include GOOSE tags.
Whether the time taken by the S4R1 OEM gateway to start communication after a power reset depends on the protocols/config used?
Yes, Initialization time will depend on the no of rows in the profile as well as the no of tags mapped.
I have recieved USB Dongle license for DLMS Explorer. How can I use it?
The dongle should be plugged to your PC before starting the DLMS Explorer application. The DLMS Explorer will then search for dongle license during the process of initialisation and if not found it will run in a demo mode.
The DLMS Explorer is getting hanged when I press "Test Configuration". What could be the issue?
It could be because of the failure of the "Test Configuration" process. Please check the "Response Timeout" parameter set in the channel which decides on how much time DLMS Explorer should wait for a response. The DLMS Explorer goes to non-responsive state till this gets timed out. Please check the query on Test Configuration failure.
When I press "Test Configuration" it is getting timed out with a failure message. What is the cause for the failure?
Test Configuration tests the basic communication with the configuration settings you have provided in the DLMS Explorer. The basic reason why it fails is due to the failure in the link. If you are sure that a proper link is given, then please check the HDLC addressing scheme and the Client Server addresses set in the explorer.
When I press "Download object list" a dialogue box with message "Download Object list failed" is shown. What could be the possible issue?
Along with the cases listed for debugging as mentioned in the Test Configuration query above, the following cases may cause failure of "Download Objectlsit". Error in Objectlist returned by server, any communication failure before receiving complete objectlist, error while reading individual object attribute of an object. In the second case please contact support@kalkitech.com with the logs in DLMS Explorer for further analysis of your issue
Is selective access by range and entry supported in DMLS Explorer?
I have recieved USB dongle license with DLMS Simulator. How can I use it?
The dongle should be plugged to your PC before starting the DLMS Simulator application. The DLMS Simulator searches for dongle license during initialisation process and if not found it then runs in a demo mode.
Does DLMS COSEM SCL support HDLC segmentation?
Yes, it supports HDLC segmentation.
Is RLRQ not handled for HDLC profile?
Presently, we support RLRQ supports only for IP based profile. As per the protocol specs RLRQ is mandatory for IP based profile and nothing is specified in case of HDLC profile.
How can I configure the IED as per my requirement based on IEC61850 standards?
You can use ICDManager provided in CD along with the delivery for modeling the IED. Please contact sales@kalkitech.com if you require any engineering help for the same.
How can I configure GOOSE and reports in IEC61850 server?
You should use ICDManager to model your IED. The GCB/RCB can be added in the ICD file to configure GOOSE and reports.
Does IEC61850 server in KSGL/SYNC has any conformance certifications?
SYNC/KSGL products have conformance certifications from KEMA/CPRI
There is no logs coming when I open diagnostic channel for IEC61850 Server. But our SCADA is able to connect to it. Why?
We have disabled the diagnostics in IEC61850 Server, since it is huge and may affect the performance of the gateway. But it will show logs of control command received and its execution status. You can use network packet analysers like wireshark to analyse the communication. Wireshark contains a packet filter for mms which is the underlying protocol used by IEC61850
I am able to connect to IEC61850 Server using my SCADA. But how can I know that the server is sending the GOOSE messages according to the configuration in icd?
Please use ethernet packet analysers like Wireshark for doing the same. Wireshark is having a packet filter for GOOSE
I am using a IEC61850 Client to browse the data from the KSGL 61850 Server. The timestamp is having a difference from the actual time.Why is that difference?
Please note that 61850 protocol displays UTC time. If you have considered this and still there is a difference, Please check the timestamp sent from your device. For more information please send a mail to support@kalkitech.com with the channel logs.
I am not able to connect to the IEC61850 server in SYNC gateway from SCADA. What could be the reason?
Firstly check if you are able to ping the gateway from SCADA. If yes try to connect to the gateway using a third party IEC61850 browsers. If the above option fails, check for any IP conflicts in the network with that of the gateway. You can also contact support@kalkitech.com with the icd file to check whether the IEC61850 Server in SYNC is properly getting initialised.
I am not getting data to the SCADA IEC61850 Client after initialization. Is it due to any configuration mistake?
Please make sure that you have configured either "Reports" or "Integrity Poll" from Client side for updation of data.
The ICD file created using ICD Manager is not getting loaded in ABB SAB600. Why is it so? Is there any error in the icd file generated by ICD Manager?
The ICD file generated by ICD Manager is as per the IEC61850 standards. But some tools like ABB SAB600, SICAM PASS etc has some manufacturer specific requirements to be met for the proper working of ICD in the application. Please contact support@kalkitech.com for further details
10.How can I check the vaildity of an ICD file?
How can I check the vaildity of an ICD file?
SCL Manager provides option for validating icd files. You can also use third party tools. Siemens provides option of validating icd file using the below link
I added GOOSE Subscriber node in IEC61850 Server Channel. But it is not working. How can I retify it?
SYNC supports GOOSE Subscriber in IEC61850 Server from GPC_V2.17.0 and above. If you are already using a compatible version please contact support@kalkitech.com with the configuration file for analysing the issue you are facing.
I am not able to connect to the IEC61850 server in SYNC gateway from SCADA. What could be the reason?
Firstly check if you are able to ping the gateway from SCADA. If yes try to connect to the gateway using a third party IEC61850 browsers. If the above option fails, check for any IP conflicts in the network with that of the gateway. You can also contact support@kalkitech.com with the icd file to check whether the IEC61850 Server in SYNC is properly getting initialised.
How should I create the ICD file to be used in IEC61850 Client?
ICD file of the server device should be used in IEC61850 Client channel during configuration
I am getting an error in traffic monitor logs saying "Error in RCB Creation". What are the possible causes?
One possible reason could be that you have enabled the report over the rcb name(eg:- rcb1) and not on its instance name(eg:- rcb101). It could also be because of an incorrect icd file used in the Client channel.
Where can I find the serial number of SYNC gateways?
In case of OEMs it is stickered on the board. In other SYNC models you can find the serial number on the gateway enclosure. If the sticker is torn or missing, please get back to us with the screenshot of "Version Information" via Easyconnect and the mac address of the gateway which can be obtained from the SCAN option in Easyconnect.
All the communications via Easyconnect are ending with error message "Failed to connect". But I can see that the gateway is responding to ping request. Please help.
Please check whether your Antivirus/Firewall settings is blocking the communication between EasyConnect and firmware. Please try after disabling the same.
A message "Firmware not running" is appears but,I try to see the logs in Traffic monitor. But I can see my device communicating with the gateway. What is wrong?
Please check whether your Antivirus/Firewall settings is blocking the communication between EasyConnect and firmware. Please try after disabling the same. Messages such as "Easyconnect is busy and try after some time" are also displayed in some cases.
What is the default IP address of the KSGL/SYNC gateways ?
Default IPs of KSGL/SYNC interfaces are as given below. Availability of the interfa depends on the gateway model.
We want to test the gateway working at our office. What all simulators can be used to test the same?
- TMW Test Harness can be used for protocols such as Modbus, DNP, IEC101/104/103
- Modtest and Modscan can be used as Modbus Clients.
- Mdbus and Mod_RSim as Modbus Servers.
- IECBrowser, IEDScout, AXS4MMS etc can be used as IEC61850 Clients.
- IEC61850 Server Simulator can be used as IEC61850 Slave
- DLMS Explorer and DLMS Simulator can be used for DLMS
- AXS4ICCP for ICCP
For quotations for TMW Test Harness, AXS4MMS, AXS4ICCP, IEC61850 Server Simulator and DLMS Explorer/Simulator please contact sales@kalkitech.com
We want to test the gateway working at our office. What all simulators can be used to test the same?
- TMW Test Harness can be used for protocols such as Modbus, DNP, IEC101/104/103
- Modtest and Modscan can be used as Modbus Clients.
- Mdbus and Mod_RSim as Modbus Servers.
- IECBrowser, IEDScout, AXS4MMS etc can be used as IEC61850 Clients.
- IEC61850 Server Simulator can be used as IEC61850 Slave
- DLMS Explorer and DLMS Simulator can be used for DLMS
- AXS4ICCP for ICCP
For quotations for TMW Test Harness, AXS4MMS, AXS4ICCP, IEC61850 Server Simulator and DLMS Explorer/Simulator please contact sales@kalkitech.com
How can I change the IP of the KSGL/SYNC gateway?
You can change the IP of the gateway only by using "IP Configuration" option available
EasyConnect.
How can I get firmware and EasyConnect for the KSGL/SYNC gateway, that I have purchased?
The KSGL/SYNC gateway it comes shipped with firmware. A CD will be shipped along with the gateway which will contain the EasyConnect Setup.
Can we redistribute the Kalki EasyConnect software configuration to our end users?
Yes, on agreement with the Software license terms.
I am getting some error when trying to run EasyConnect.
EasyConnect_V3.x.x and above requires Dot Net Framework v2.0 or above to be installed.Please check whether the corresponding version is available in your PC
I am not able to get the gateway in SCAN. What should I do?
Your antivirus software or firewall may be blocking the multicast messages. Please disable
these and try once again.
Which are the gateway models with serial port surge protection?
All the SYNCSxR1 gateway models has got surge protection.
What is the console port? Is it ethernet port or serial port? How can I use it? What type of cable I must use?
Console port is a serial port used for debugging critical issues. The login and other information can be obtained from KALKITECH Support in such cases. A serial cross cable (RJ45 to DB9) should be used for the same. The RS232 settings are given below :
Baud Rate – 115200
Data Bit – 8
Stop Bit – 1
Parity – None
Flow Control – None.
What is the serial port pin configuration for the gateway I am using?
Please refer the SYNC User manual for details.
I have a KSGL S6R1 and KSGL S4R2. Are the serial port pin outs the same?
No. The pin outs are different for the models specified. Please refer KSGL/SYNC User Manual for details.
I want to change the dip switch settings in the gateway for converting the serial port to RS485 mode. But there is a "Warranty void if removed" seal. What should I do?
For setting the jumper, the gateway enclosure can be removed. For keeping the warranty, get the confirmation from the Kalkitech support for the specific gateway unit. i.e., the customer can email the gateway serial no and get the confirmation from support@kalkitech.com
"Respond Data not available" in my Master for Class 2 polls. Why does this message gets displayed?
This happens because there is no sample in IEC101 Slave to respond to your query. The samples are created in cyclic timeout. And once responded for a poll, it will respond "Respond Data not available" till next sample happens. Else there should be an availablility of spontaneous data which can be reported in response to Class 2 poll if cyclic data is not available.
I have recieved the usb dongle license for SCL Manager. How can I use it?
The dongle should be plugged to your PC before starting the SCL Manager application. The SCL Manager looks for the dongle license during initialisation and if not found it runs in demo mode.
I am inducing an event in the relay. But it is not getting reported in the upstream protocol. What may be the problem?
Please check whether you have enabled event poll. If yes please run traffic monitor for courier channel and check whether the event generated is shown in the log when it is induced. If shown confirm whether the ROW COLUMN of the event reported from the relay is same as the one you are expecting the event and configured in the profile.
Which all courier relays are supported in SYNC?
As of now our Courier Master is tested with P series relays and we have successfully commissioned many project which involves P122,P342,P343,P442,P443,P922 etc. For K-Series relays all the functionalities are not available. Please contact sales@kalkitech.com for getting firmware changes done to support your corresponding relay.
What functions defined in NMEA are supported in SYNC?
GPZDA. Please refer to SYNC-NMEA user manual for frame format and more details.
Which simulator can be used to test NMEA in SYNC?
You can use NEMA Talker which is a third party tool.
Do we require separate licenses for Modbus master and slave?
Yes. Separate licenses are required for configuring Modbus Master and Modbus Slave
Do we require separate license for Modbus TCP and Modbus SERIAL protocols?
No. You don't require separate licenses.
In EasyConnect I can see an option "IP address of remote" is it mandatory ?
In the case of Modbus master the IP Address of remote host should be entered in the field provided but for modbus slave,you can proceed with IP as 0.0.0.0, if there is only one modbus slave is listening.
Am having an address 40001 how can I configure in modbus ?
This 40001 address will be a holding register with an offset 40000. In order to configure this in EasyConnect you can add a holding register with start address 1. Instead of that if you are configuring 40001 without the offset in EasyConnect it will be treated as an actual address and may not get proper results.
How time sync is done in modbus ?
Detailed descrption is given in manual ie, the from start address, 7 registers are used for synchronization.
Whether dead band value is considered after scaling ?
Yes, only after scaling the dead band is considered
Getting NACK messages in EC diagnostics channel for master?.
NACK implies no acknowledgement means the corresponding point is not present in the external slave device.
Getting header time out in EC diagnostics ?
Header time out shows that there is no response received from the external slave device. It could be due to a no of reasons. Some of them are listed below:
- No proper connectivity with the external slave. Cross check the communication cables used.
- Not able to receive the packets within the header time out ie. Device responds very slow.Increase the header time out
- The data is received with error on the other side. Could be due to serial port/UART damage.Get a new unit via RMA.
Do we require licenses for DNP Master and Slave?
Yes, separate licenses are required to configure DNP Master and DNP Slave.
Do we require separate license for DNP TCP and DNP SERIAL protocols?
No, it not require. For eg:- If you have purchased a DNP MASTER license, you can use it either as TCP mode or SERIAL mode.
DNP Master/Slave is not communicating with its peer. What could be the problem?
The Channel Parameters configured in EasyConnect should match with that of the peer of the DNP Channel configured.
What are the objects supported in DNP?
Please refer Appendix A in DNP3 User Manual.
What should be the addresses configured in the Source/Destination Address rows in the DNP Node?
Source address should be the address of the device which is being configured and destination address should be the address of the peer.
Is there an option to configure transparent channel output linked to a DNP 3.0 channel? Is relay configuration option available through a DNP Channel configured?
How is Object 2 reported in SYNC, when there is no specific configuration option avaible?
Data in DNP 3.0 can be updated by following methods:
- DNP Master doing a specific object read.
- DNP Master doing a Class 0 poll.
- DNP Out station reporting data as an event.
Binary Input will be reported as Object 1(Static Object) for Class 0 poll and as Object 2(Change event Object), for any of the event poll.
Class 1/2/3 requests responds with "No Data" while Class 0 requests gives data. Why?
As Class 1/2/3 requests are made to update any of Class 1/2/3 events in the outstation. Only change events will be reported in Class 1/2/3 response. In case of no change events, "No Data" response would be sent. While, in Class 0 poll, all the Static data will be updated. It's similar to integrity poll in IEC60870-5-101.
Unsol Events are not getting reported in DNP Master. Why?
"Unsol Command Type at Restart IIN" parameter in DNP Master Node should be enabled to enable Unsol reporting of events. Note: To enable unsol in relay.
How can we configure Unsolicited response in DNP Slave?
The configuration options are there in DNP Slave node section, "Unsolicited Response Config".
My points in Object 1 are always getting reported in variation 1 even though I configured the same in Variation 2 in the DNP profile. Why?
The Default variations set in Node is taken in priority over the variations set in profile. If you want a point to get reported in the variation set in profile, the default variation for the corresponding Object in Node should be made to '0'.
Will all gateway models support SNMP?
No. Please contact support@kalkitech.com for more details
Do I have to purchase ICCP Client and server license separately?
No. ICCP is a peer protocol and you can configure both server and client with the same license.
Is it possible to setup VPN over GPRS/CDMA?
Which variant of VPN is used in SYNC gateways?
Will all gateway models support VPN?
No. Please contact support@kalkitech.com for further information.
What are the files necessary for running server/client simulator in PC?
ca.crt, ca.key, dh1024.pem, and the respective .crt and .ket files of server/client
How do I run VPN server/client in a PC?
Right click on the server.ovpn/client.ovpn and select "Start OpenVPN" from the context menu.
.I have started OpenVPN. But some error message is displayed?. After pressing any key the window closes. What could be the reason?
You have to rename the files EasyConnect.crt and EasyConnect.key to server/client.crt and server/client.key as per the requirement. If still the issue persists please contact support@kalkitech.com.
Logs in VPN window stops once the initialisation is completed. There is no communication. Whats the reason?
Antivirus/firewall may be blocking the connections. Please disable the same and try again.
How can we finally infer that VPN configuration is correct, working and ready for communication?
How can we finally infer that VPN configuration is correct, working and ready for communication?
I was using EasyConnect_V3.x.x. What is new in EasyConnect_V4.x.x?
EasyConnect_V4.0.0 allows configuration of multiple devices and save it in a single project(.ecc) file. It also allows features like VPN/SNMP/Dialup configuration for the KSGL/SYNC gateways.
What does .ecc and .xml formats mean? How can we save .xml in EasyConnect?
EasyConnect supports configuration of multiple device in a project from V4.0.0 differing from configuration of a single device in earlier versions. The atomic part to be downloaded to a gateway is the configuration file(.xml). The project file(.ecc) contains configuration of multiple devices from which EasyConnect allows downloading the configuration of the corresponding device. You can import a device configuration to the project by right clicking on the "device" node in the project tree and selecting "Import device config file". You can also export the configuration of an individual device by right clicking on the "Protocol Configuration" node under the corresponding device and selecting "Export device config file".
An error message "Firmware not running" appears in diagnostics window. But all the communication with external master/slave are working fine. Why it is so ?
This a very common message that pop up when Windows firewall/Antivirus blocks this Easyconnect functionality. Please disable both and try again, also there may be some messages like "No support for timezone","EasyConnect is busy, Try after sometime" while trying for diagnostics. These are also due to the above reason.
SCAN command gives a message "blocking operation was interrupted by a call to WSAcancelBlockingcall". Please clarify?
Anitvirus is blocking the port (2001) which is used by Easyconnect for this functionality. Please, unblock the same and try again.Also please note that this pop up message varies according to the Antivirus Software.It may be "An invalid argument has specified" depending on the anitvirus running on that PC.
None of the Easyconnect features are working except SCAN. For all other features a pop up message stating the "host has failed to respond". But I can see that the upstream/downstream communcations are working fine and also SCAN is detecting the device.
Anitvirus is blocking the port (2500) which is the remote port for easyconnect for all other functionalites except SCAN. Please unblock the same and try again.
"Sync Disk..." is coming in the LCD display. What should I do?
Please contact support@kalkitech.com for a solution
How can I configure HSB Channels in main and standby gateways?
The configuration of both main and standby should be same except for some parameters in HSB channel. IP Address and Redundant IP Address among the channel parameters, and HSB Type in the HSB node. The IP Address fields should be the IP of the interface of the peer gateway which acts as integrated link. HSB Type of one gateway should be main and other should be standby.
I am using HSB in IP swapping mode. Both my gateways are getting HOT and are having the same IP. What could be the issue?
The basic cause of the above issue is that there is no integrity link between the hot and standby gateway. Check whether the physical interface link is correct and the IPs provided in the HSB Channel of main and standby gateways are the corresponding IP of the remote gateway interface to which the IL is connected. The issue can also happen if there is a mismatch in the database of both the gateways. Please check if both the gateways have same configuration as explained in the configuration of HSB Channels above.
Will all SYNC gateways and models support PPP?
No, An update package is required to be downloaded in the gateway for enabling PPP. Please contact support@kalkitech.com for more details
Is it manadatory to add client/server name and password in Dialup settings?
The PPP is not becoming up when I changed the modem. How can I debug this issue?
A dialscript executed in the gateway, which are a set of commands for the modem, dials and establishes the connection. Some AT commands supported by modems are manufacturer dependent. Please contact support@kalkitech.com with the AT commands list supported by your modem.
Can I get the logs for PPP?
Yes, Logs can be taken from Easyconnect, Diagnostics-->Application Logs. This should be used only for debug purpose. While activating logs the exiting connection if any will be disconnected and the system will try to reconnect and the corresponding logs will be saved till it is stopped by the user. Please remeber that PPP will be stopped whenever the logs is stopped from the easyconnect. So for re-establishing the PPP connection the gateway has to be restarted.
I am not able to update firmware to SYNC 2000 S2R1. A message "The requested FTP command is not supported when using http proxy" appears. What should I do?
Please disable the proxy settings in your browser and try again. Moreover we suggest to use ethernet cross cable and directly connect from your PC to the gateway during firmware updation in SYNC 2000 S2R1 devices.
How can I change the serial ports in SYNC 2000 S2R1 to RS485?
You should change the dip switches available on SYNC 2000 S2R1 to change the serial ports to RS485.
Can I use COM2 for a PPP channel over GPRS/CDMA ?
No. The COM2 port does not have a DCD line and it can't be used for PPP. COM1 can be used from PPP.
Can I enable hardware clock as well as hardware flow control simultaneously?
No. The RTS-CTS hardware flow control signals are used for the additional hardware clock circuit.
What are the firmware recovery modes available in SYNC 2000 S2R1?
The emergency mode and firmware fault recovery mode are detailed in section 5 of KSGL/S user manual.
Can I restart the protocol conversion engine without restarting SYNC 2000 S2R1?
No. For restarting the firmware SYNC 2000 S2R1 should be restarted.
What are the additional functions available in SYNC 2000 S2R1 when compared to S2OEM.?
SYNC has got the hardware clock where as S2OEM consist only the software clock.
SYNC S4 R1 OEM _What is the average power consumption of the module under normal working conditions?
Under normal working conditions the average power consumption will be around 1.6W. Please note that the current consumption will increase as per the number of serial ports used.
Is the Ethenet interface isolated from the rest of the circuit? If so, what is the level of isolation?
Yes. The Ethernet RJ45 port has an inbuilt 1.5kV isolation.
How can I use the debug port available in S4OEM?
The debug port can be used connecting the DRXD and DTXD to computer through TTL to RS232 converter using serial cross-over cable.
What is the maximum number of datasets that can be created in S4OEM?
The maximum number of datasets that can be created in SYNC S4 OEM is 15 with maximum tags per dataset as 50, also the total no of tags which can be configured is 800 which includes GOOSE tags.